AM✴✴✴XMDEH SeriesAM✴✴✴XMDGH SeriesAir Conditionerinstallation manualimagine the possibilitiesThank you for purchasing this Samsung product.DB68-03941A
10Installation locationMoving the Outdoor Unitf Select the moving route in advance.f Be sure that moving route is safe from the weight of the outdoo
11ENGLISHBase ground work< When installing on the ground >Drain hole 150mm or more< When installing on the roof >Install the outdoor unit
12Refrigerant pipe installationRefrigerant pipe work f The length of refrigerant pipe should be as short as possible and the height dierence between
13ENGLISHSelecting refrigerant pipe Temper grade and minimum thickness of the refrigerant pipeOuter diameter [mm] Minimum thickness [mm] Temper gradeø
14Refrigerant pipe installationSelecting Y-jointf Select the rst Y-joint according to main pipe size of each outdoor unit capacity.f Select the oth
15ENGLISHDirection of the pipe when brazingf Brazing the pipe should be done with the pipe headed downward or horizontally.f Avoid brazing with the
16Refrigerant pipe installationTightening are connection area f Check that the aring is properly made.f Align the center of the piping and sucien
17ENGLISHPipe installation for an outdoor unitPipe directionThe refrigerant pipe can be pulled out from front, ank, rear, and bottom side, so install
18Refrigerant pipe installationRefrigerant pipe installation examplesUsing a Y-joint Using a Y-joint/EEV kitUsing a header joint Using a header joint/
19ENGLISHClassication Y-joint connection Y-joint / EEV kit connectionMaximum allowable length of pipeOutdoor unit ~ Indoor unitsActual LengthThe dist
2ContentsSafety precautions ... 3Outdoor unit typ
20Refrigerant pipe installationConnection by header jointgOutdoor unitHeader jointIndoor unitConnection by Y-joint/header jointH2H1f cg Outdoor unitIn
21ENGLISHRefrigerant pipe workRefrigerant Y-joint installation Install the Y-joint ‘horizontally’ or ‘vertically’.f Install horizontallyf Install ve
22Refrigerant pipe installationCorrect use (The insertion depth of connecting pipe)Incorrect use(The insertion depth of connecting pipe)Basic specica
23ENGLISHt When using A~J type of header joint, connect the header joint to the pipe with provided reducer. t When using K~Z type of header joint, c
24Refrigerant pipe installationPerforming air tightening testf Use tools for R-410A only to prevent the inow of foreign substances and to resist the
25ENGLISHVacuuming a pipe and an indoor unitf Use the tools for R-410A only to prevent the inow of foreign substances and resist against the interna
26Refrigerant pipe installationSelecting additional refrigerant chargingf Basic refrigerantThe basic amount of additional refrigerant charged at a fa
27ENGLISH2. The amount of additional refrigerant for each indoor unit(Unit : kg)Capacity (kW)Model1.5 1.7 2.2 2.8 3.6 4.5 5.6 6 7.1 8.2 9 11.2 12.8 1
28Refrigerant pipe installationf Be sure to plug the rest of drain holes not connected with drain plugs using drain caps.Drain capDrain plugInsulatin
29ENGLISHInsulating refrigerant pipef You must insulate refrigerant pipe, Y-joint, header joint, and pipe connection area.f If you insulate the pipe
3ENGLISHSafety precautionsCarefully follow the precautions listed below because they are essential to guarantee the safety of the equipment.WARNINGt
30Refrigerant pipe installationInsulating the header jointf Fasten the header joint using a cable tie and cover the connected part.f Insulate the he
31ENGLISHWiring workf Wiring work should be performed in accordance with related laws such as ‘Technical specication on electric installation’, ‘Wir
32Wiring workOverall System CongurationConnection of the power cable (1 phase 2 wires)Distribution board Outdoor unit Indoor unitCommunication cable2
33ENGLISHConnection of the power cable (3 phase 4 wires)Distribution board Outdoor unit Indoor unitCommunication cable220VWired remote controllerEarth
34Wiring workSpecication for circuit breaker and power supply cordf Power supply cord is not supplied with air conditioner.f Select the power suppl
35ENGLISHSelecting compressed ring terminalf Select a compressed ring terminal of a connecting power cable based on a nominal dimensions for cable.f
36Wiring workInstalling grounding wiref Grounding must be done by a qualied installer for your safety.f Use the grounding wire by referring to the
37ENGLISHGrounding workIf the power distribution circuit does not have a grounding or the grounding does not comply with specications, a ground rod m
38Setting indoor unit option switch and key functionPBA shapeAM✴✴✴✴XMD✴H Series7-SEGMENT (DISPLAY)DIP S/W (K5~K16)Do not connect wires to these termin
39ENGLISHSetting the number of connecting indoor unitsEx : When you connect 3 indoor units, set SW02 to 3AM✴✴✴✴XMD✴H SeriesSW02Unit digitSW01Unit digi
4Safety precautionsInstalling the unitIMPORTANT: When installing the unit, always remember to connect rst the refrigerant tubes, then the electrical
40Setting indoor unit option switch and key functionDIP S/W specication settingAM✴✴✴✴XMD✴H SeriesTAC T switchNumber of pressesContent SEG1 SEG2 SEG3
41ENGLISHf K5 : Automatic / Manual Silent mode operation settingSwitchFunction (Silent mode operation control)K5ON Automatic Silent mode operationOFF
42Setting indoor unit option switch and key functionf K11, K12: Changing heating capacity correction tableSwitchFunctionK11 K12ON ON DefaultON OFF D
43ENGLISHf K15, K16: Defrost Option l This is to control entering condition of defrost modeSwitchFunctionK15 K16ON ON MIDON ON LOW1OFF OFF LOW2 ❋ Def
44Setting indoor unit option switch and key function ❋ While you are setting the option, you may press and hold the K1 button to reset the value to pr
45ENGLISHInspection before check operation1. Check the power cable and communication cable of the indoor and outdoor unit.2. Supply power to the out
46Inspection and check operationCheck operation1. Use KEY MODE to run check operation. - When the check operation is not completed, UP (unprepared) w
47ENGLISHCharging refrigerantRefrigerant type GWP valueR-410A 2088Unit kg tCO2e①, a②, b① + ②, ct GWP=Global Warming Potentialt Calculating tCOe : k
48Pump DownThe object of pump downf You can reduce as much refrigerant leakage as possible during product movement or repair by collecting the refrig
49ENGLISHHow to put the refrigerant into the refrigerant container before pump down operation ❋ When the amount of refrigerant charged in the system e
5ENGLISHOutdoor unit type ShapeModel Cooling and Heating1phaseAM040✴XMDEHAM050✴XMDEHAM060✴XMDEH 3phaseAM040✴XMDGHAM050✴XMDGHAM060✴XMDGH Installation
50Checking lists after nishing installationf Before supplying power, measure the power terminal (L, N) and outdoor unit grounding using insulation-r
51ENGLISHTrial operationf Check the power supply between the outdoor unit and the cabinet panel. - 1 phase power supply : L, N - 3 phase power suppl
6Deciding to where to install the outdoor unitDecide the installation location based on the following condition and obtain the user’s approval. f Avo
7ENGLISHt Install the indoor unit away from any interfering sources such as radio, computer, stereo equipment and also select a place where the elect
8Installation locationf Make a space for ventilation and service as seen in the picture.f When multiple outdoor units are combined for installation,
9ENGLISHWhen installing more than 1 outdoor unit ❋ When 3 sides of the outdoor unit are blocked by the wall (Unit : mm)300 or more300 or more 600 or m