Samsung AM060FXMDEH Manuale Utente

Navigare online o scaricare Manuale Utente per no Samsung AM060FXMDEH. Samsung AM050FXMDEH Installation guide Manuale Utente

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa

Sommario

Pagina 1 - Air Conditioner

AM✴✴✴XMDEH SeriesAM✴✴✴XMDGH SeriesAir Conditionerinstallation manualimagine the possibilitiesThank you for purchasing this Samsung product.DB68-03941A

Pagina 2 - Contents

10Installation locationMoving the Outdoor Unitf Select the moving route in advance.f Be sure that moving route is safe from the weight of the outdoo

Pagina 3 - Safety precautions

11ENGLISHBase ground work< When installing on the ground >Drain hole 150mm or more< When installing on the roof >Install the outdoor unit

Pagina 4

12Refrigerant pipe installationRefrigerant pipe work f The length of refrigerant pipe should be as short as possible and the height dierence between

Pagina 5 - Installation combination

13ENGLISHSelecting refrigerant pipe Temper grade and minimum thickness of the refrigerant pipeOuter diameter [mm] Minimum thickness [mm] Temper gradeø

Pagina 6

14Refrigerant pipe installationSelecting Y-jointf Select the rst Y-joint according to main pipe size of each outdoor unit capacity.f Select the oth

Pagina 7 - 1.5m or more

15ENGLISHDirection of the pipe when brazingf Brazing the pipe should be done with the pipe headed downward or horizontally.f Avoid brazing with the

Pagina 8

16Refrigerant pipe installationTightening are connection area f Check that the aring is properly made.f Align the center of the piping and sucien

Pagina 9

17ENGLISHPipe installation for an outdoor unitPipe directionThe refrigerant pipe can be pulled out from front, ank, rear, and bottom side, so install

Pagina 10 - Installation location

18Refrigerant pipe installationRefrigerant pipe installation examplesUsing a Y-joint Using a Y-joint/EEV kitUsing a header joint Using a header joint/

Pagina 11 - Base ground work

19ENGLISHClassication Y-joint connection Y-joint / EEV kit connectionMaximum allowable length of pipeOutdoor unit ~ Indoor unitsActual LengthThe dist

Pagina 12 - Refrigerant pipe installation

2ContentsSafety precautions ... 3Outdoor unit typ

Pagina 13 - Selecting refrigerant pipe

20Refrigerant pipe installationConnection by header jointgOutdoor unitHeader jointIndoor unitConnection by Y-joint/header jointH2H1f cg Outdoor unitIn

Pagina 14

21ENGLISHRefrigerant pipe workRefrigerant Y-joint installation Install the Y-joint ‘horizontally’ or ‘vertically’.f Install horizontallyf Install ve

Pagina 15 - Cutting or Flaring the pipes

22Refrigerant pipe installationCorrect use (The insertion depth of connecting pipe)Incorrect use(The insertion depth of connecting pipe)Basic specica

Pagina 16

23ENGLISHt When using A~J type of header joint, connect the header joint to the pipe with provided reducer. t When using K~Z type of header joint, c

Pagina 17 - Pipe direction

24Refrigerant pipe installationPerforming air tightening testf Use tools for R-410A only to prevent the inow of foreign substances and to resist the

Pagina 18

25ENGLISHVacuuming a pipe and an indoor unitf Use the tools for R-410A only to prevent the inow of foreign substances and resist against the interna

Pagina 19

26Refrigerant pipe installationSelecting additional refrigerant chargingf Basic refrigerantThe basic amount of additional refrigerant charged at a fa

Pagina 20

27ENGLISH2. The amount of additional refrigerant for each indoor unit(Unit : kg)Capacity (kW)Model1.5 1.7 2.2 2.8 3.6 4.5 5.6 6 7.1 8.2 9 11.2 12.8 1

Pagina 21 - Refrigerant pipe work

28Refrigerant pipe installationf Be sure to plug the rest of drain holes not connected with drain plugs using drain caps.Drain capDrain plugInsulatin

Pagina 22

29ENGLISHInsulating refrigerant pipef You must insulate refrigerant pipe, Y-joint, header joint, and pipe connection area.f If you insulate the pipe

Pagina 23 - Gas side

3ENGLISHSafety precautionsCarefully follow the precautions listed below because they are essential to guarantee the safety of the equipment.WARNINGt

Pagina 24

30Refrigerant pipe installationInsulating the header jointf Fasten the header joint using a cable tie and cover the connected part.f Insulate the he

Pagina 25 - 0.05MPa (gauge pressure)

31ENGLISHWiring workf Wiring work should be performed in accordance with related laws such as ‘Technical specication on electric installation’, ‘Wir

Pagina 26

32Wiring workOverall System CongurationConnection of the power cable (1 phase 2 wires)Distribution board Outdoor unit Indoor unitCommunication cable2

Pagina 27

33ENGLISHConnection of the power cable (3 phase 4 wires)Distribution board Outdoor unit Indoor unitCommunication cable220VWired remote controllerEarth

Pagina 28

34Wiring workSpecication for circuit breaker and power supply cordf Power supply cord is not supplied with air conditioner.f Select the power suppl

Pagina 29 - Insulating refrigerant pipe

35ENGLISHSelecting compressed ring terminalf Select a compressed ring terminal of a connecting power cable based on a nominal dimensions for cable.f

Pagina 30

36Wiring workInstalling grounding wiref Grounding must be done by a qualied installer for your safety.f Use the grounding wire by referring to the

Pagina 31 - Wiring work

37ENGLISHGrounding workIf the power distribution circuit does not have a grounding or the grounding does not comply with specications, a ground rod m

Pagina 32

38Setting indoor unit option switch and key functionPBA shapeAM✴✴✴✴XMD✴H Series7-SEGMENT (DISPLAY)DIP S/W (K5~K16)Do not connect wires to these termin

Pagina 33

39ENGLISHSetting the number of connecting indoor unitsEx : When you connect 3 indoor units, set SW02 to 3AM✴✴✴✴XMD✴H SeriesSW02Unit digitSW01Unit digi

Pagina 34

4Safety precautionsInstalling the unitIMPORTANT: When installing the unit, always remember to connect rst the refrigerant tubes, then the electrical

Pagina 35 - Silver solder

40Setting indoor unit option switch and key functionDIP S/W specication settingAM✴✴✴✴XMD✴H SeriesTAC T switchNumber of pressesContent SEG1 SEG2 SEG3

Pagina 36

41ENGLISHf K5 : Automatic / Manual Silent mode operation settingSwitchFunction (Silent mode operation control)K5ON Automatic Silent mode operationOFF

Pagina 37 - Grounding work

42Setting indoor unit option switch and key functionf K11, K12: Changing heating capacity correction tableSwitchFunctionK11 K12ON ON DefaultON OFF D

Pagina 38 - PBA shape

43ENGLISHf K15, K16: Defrost Option l This is to control entering condition of defrost modeSwitchFunctionK15 K16ON ON MIDON ON LOW1OFF OFF LOW2 ❋ Def

Pagina 39 - S/W function

44Setting indoor unit option switch and key function ❋ While you are setting the option, you may press and hold the K1 button to reset the value to pr

Pagina 40 - DIP S/W specication setting

45ENGLISHInspection before check operation1. Check the power cable and communication cable of the indoor and outdoor unit.2. Supply power to the out

Pagina 41

46Inspection and check operationCheck operation1. Use KEY MODE to run check operation. - When the check operation is not completed, UP (unprepared) w

Pagina 42

47ENGLISHCharging refrigerantRefrigerant type GWP valueR-410A 2088Unit kg tCO2e①, a②, b① + ②, ct GWP=Global Warming Potentialt Calculating tCOe : k

Pagina 43 - Setting the option

48Pump DownThe object of pump downf You can reduce as much refrigerant leakage as possible during product movement or repair by collecting the refrig

Pagina 44

49ENGLISHHow to put the refrigerant into the refrigerant container before pump down operation ❋ When the amount of refrigerant charged in the system e

Pagina 45 - Outdoor temperature (°C)

5ENGLISHOutdoor unit type ShapeModel Cooling and Heating1phaseAM040✴XMDEHAM050✴XMDEHAM060✴XMDEH 3phaseAM040✴XMDGHAM050✴XMDGHAM060✴XMDGH Installation

Pagina 46 - Charging refrigerant

50Checking lists after nishing installationf Before supplying power, measure the power terminal (L, N) and outdoor unit grounding using insulation-r

Pagina 47

51ENGLISHTrial operationf Check the power supply between the outdoor unit and the cabinet panel. - 1 phase power supply : L, N - 3 phase power suppl

Pagina 49

6Deciding to where to install the outdoor unitDecide the installation location based on the following condition and obtain the user’s approval. f Avo

Pagina 50

7ENGLISHt Install the indoor unit away from any interfering sources such as radio, computer, stereo equipment and also select a place where the elect

Pagina 51 - Trial operation

8Installation locationf Make a space for ventilation and service as seen in the picture.f When multiple outdoor units are combined for installation,

Pagina 52

9ENGLISHWhen installing more than 1 outdoor unit ❋ When 3 sides of the outdoor unit are blocked by the wall (Unit : mm)300 or more300 or more 600 or m

Commenti su questo manuale

Nessun commento