9-2. Operation limit
5) RC060DHXEA
6) RC071/090/100/125/140D(P,Z)HXE7, RC090/100SHXE7
7) RC052/071SHXE7
Mode
Outdoor Indoor Indoor
Temperature (DB) Temperature (DB) Humidity (RH)
Cooling -15°C ~ 46°C 18°C ~ 32°C
80% or less Heating -20°C ~ 24°C 27°C or less
Drying -15°C ~ 46°C 18°C ~ 32°C
Mode
Outdoor Indoor Indoor
Temperature (DB) Temperature (DB) Humidity (RH)
Cooling -15°C ~ 50°C 18°C ~ 32°C
80% or less Heating -20°C ~ 24°C 27°C or less
Drying -15°C ~ 50°C 18°C ~ 32°C
Mode
Outdoor Indoor Indoor
Temperature (DB) Temperature (DB) Humidity (RH)
Cooling -5°C ~ 43°C 18°C ~ 32°C
80% or less Heating -15°C ~ 24°C 27°C or less
Drying -5°C ~ 43°C 18°C ~ 32°C
X The standardized temperature for heating is 7°C DB. If the outdoor temperature drops to 0°C DB or below,
the heating capacity can be reduced depending on the temperature condition.
If the cooling operation is used at over 32°C DB, it does not cool at its full capacity.
X The use of the air conditioner at a relative humidity above the expected one (80%) may cause the formation of